Consensus is that the problem is caused by getty and the UPS software both
running on the same serial port. Solution is to either redefine the console
or use a splitter cable on the E450, which has a combined serial port as
opposed to two separate A/B connections.
Thanks to:-
John Stoffel
Thomas M. Payerle
francisco
Tim Evans
Rob Windsor
Brad Morrison
As usual, the list produced a better response in a shorter time than vendor
support.
Original question below:-
I have an E450 running Solaris 7. I have tried to install and APC SmartUPSUPS
and the associated power management software on this server, however when
the UPS is connected via the supplied serial cable the server refuses to
boot. Disconnecting the cable allows the server to boot, and I can see the
following appear in /var/adm/messages:-
Apr 27 11:38:39 myhost upsd[2933]: Unable to communicate with UPS
Apr 27 11:38:39 myhost unix: envctrl: ignoring debug enter sequence
Apr 27 11:39:32 myhost last message repeated 1182 times
Apr 27 11:40:01 myhost login: REPEATED LOGIN FAILURES ON /dev/console
Any ideas as to how I can get this working. I have previously used this
and software on an E250 with the same release of the OS no problems
--
Kevin Davidson | UNIX Systems Administrator
Computers Unlimited | www.unlimited.com
020 8358 9126 | kdavidson@xxxxxxxxxxxxx
_______________________________________________
sunmanagers mailing list
sunmanagers@xxxxxxxxxxxxxxx
http://www.sunmanagers.org/mailman/listinfo/sunmanagers
- Prev by Date: SUMMARY: Trouble with Environmental variables in crontab
- Next by Date: SUMMARY: how to carry out E250 maintenance?
- Previous by thread: SUMMARY: Trouble with Environmental variables in crontab
- Next by thread: awk - command line works / script doesn't
- Index(es):
Relevant Pages
|
|