First we define a computer grade UPS. This one outputs a
modified sine wave. That means unloaded in battery backup
mode, the 120 VAC output is two 200 volt square waves with a
270 volt spike between those square waves. This 'dirty'
output may be destructive to small electric motors. But the
output is only intended for powering computers. Computer
power supplies are so resilient that 'computer grade' UPSes
can output some of the 'dirtiest' electricity.
This 'dirty' electrical output when in battery backup mode
is why UPS manufacturers quietly suggest using no power strip
protectors on a UPS output. Even Best made this 'no
protector' recommendation, even though their Ferrup UPSes had
a lowest total harmonic distortion.
These manufacturers play games with the expression 'sine
wave'. Pure sine wave means what? Nothing technical. The
expression is to confuse those who would represent color
glossy sales brochures as if numerical specifications. Even
the word 'dirty' is a misnomer. What is dirty? Too much
voltage? Not enough voltage? Too much noise? Too high total
harmonic distortion? Loss of power for 1/2 of a sine wave?
All might be a problem. So which one defines 'dirty'?
Each type of power problem must be addressed separately.
Most problems are solved by a power supply that meets minimum
standards - such as those defined in Intel specs. Standards
that existed even 30 years ago.
Ferrups promoted 'big iron' solutions for better filtering.
But they forget to mention, for example, that safety ground
wire carries destructive transients completely around the UPS
and directly into computer motherboard. What has the Ferrup
provided? Filtering that the computer power supply really
does not require. If I was using a sophisticated analog
system, then I might consider a Ferrup for its cleaner power.
But the advantages of a Ferrup provide little advantage to a
computer.
In summary, what constitutes a good UPS depends on which
kind of 'dirty' is being solved.
A computer must work just fine even when voltage drops so
low that incandescent lamps are at less than 40% intensity.
Supply must withstand (without damage) short transients of
over 1000 volts. Power supply must work just fine even when
the AC power is lost for 17 milliseconds. Again, defacto
industry standards. Computers are quite resilient. However
internal protection assumes a typically destructive transient
will be earthed at the service entrance. 'Whole house'
protection is required so that a transient will not overwhelm
computer's and UPS's internal protection. Yes, even the
control electronics in a UPS require and therefore have
internal protection.
That leaves only blackouts and extreme brownouts as the
remaining unsolved significant problem. Most every UPS solves
that problem. Some do it better by maintaining power longer,
switching to batteries less frequently (Automatic Voltage
compensation), and sending warning signals to the computer.
However, many plug-in UPSes are designed so cheaply as to
expire the battery about every 3 years. Ironic. Even car
batteries exposed to harsh outside environments now last seven
years. In serious UPS systems, batteries are now lasting
something short of 20 years. Obviously more money will buy a
UPS with a better battery. But how do you discover which
provides the better battery / battery charging system? Easier
to just confirm the UPS uses an industry standard battery that
you can replace every 3 years without factory service. And
yes, some UPSes do use proprietary batteries that sometimes
costs almost as much as a new UPS.
IOW just about any UPS of sufficient power will perform fine
for a computer since 1) a computer power supply is so
resilient, 2) the UPS is for data protection from blackouts
and extreme brownouts, 3) and other power protection problems
must be addressed elsewhere as part of a building wide
solution. Yes, that is a 'building wide' solution as even
Montandon and Rubenstein demonstrate in a 4 Nov 1998 paper in
the IEEE Transactions on Electromagnetic Compatibility - if
one desires Data Center type reliability.
An overview about power protection - and why a more
expensive Ferrup provided so little to a system wide solution.
jordan@ccs4vms.com wrote:
> w_tom,
> thanks for all the useful info. Do you have info/opinion on the
> 'higher grade' UPS models, like the Best FERRUPS, as far as power
> conditioning and protection from 'other than surge' power problems
> (like brownouts)?
>
> My previous employer always wanted the FERRUPS units for critical
> systems (not that they always had the budget), and if I had a
> commercial budget instead of a hobbyist budget (hence the APC Backups
> Pro 1100) they're still what I'd look at getting (whatever the current
> owner's name is; I know Best got bought out).
>
> Thanks again for all the info!
>
> Rich
- Next message: w_tom: "Re: UPS/Power conditioning questions"
- Previous message: JF Mezei: "Re: Telephony systems on VMS"
- In reply to: jordan_at_ccs4vms.com: "Re: UPS/Power conditioning questions"
- Next in thread: DL Phillips: "Re: UPS/Power conditioning questions"
- Messages sorted by: [ date ] [ thread ] [ subject ] [ author ]
Relevant Pages
|